Selamat Pagi Semua,pagi ini saya akan malampirkan foto EXV chiller Carrier yang telah di ganti oleh the bokis (MAQNA COOLTECH ).
وَ السَّلاَمُ عَلَيْكُمْ وَرَحْمَةُ اللهِ وَبَرَكَاتُهُ
Refrigerant
|
Chemical Name
|
Color Code
|
R11
|
Trichlorfluoromethane
|
Orange
|
R12
|
Dichlorodifluoromethane
|
White
|
R13
|
Chlorotrifluoromethane
|
Light Blue
|
R113
|
Trichlorotrifluoroethane
|
Dark Purple
|
R114
|
Dichlorotetrafluoroethane
|
Navy Blue
|
R12/114
|
Dichlorodifluoromethane, Dichlorotetrafluoroethane
|
Light Gray
|
R13B1
|
Bromotrifluoromethane
|
Pinkish-Red
|
R-22
|
Chlorodifluoromethane
|
Light Green
|
R-23
|
Trifluoromethane
|
Light Blue Gray
|
R123
|
Dichlorotrifluoroethane
|
Light Blue Gray
|
R124
|
Chlorotetrafluoroethane
|
DOT Green
|
R134a
|
Tetrafluoroethane
|
Light Blue
|
R401A
|
Chlorodifluoromethane, Difluoroethane,
Chlorotetrafluoroethane
|
Pinkish-Red
|
R401B
|
Chlorodifluoromethane, Difluoroethane,
Chlorotetrafluoroethane
|
Yellow-Brown
|
R402A
|
Chlorodifluoromethane, Pentafluoroethane, Propane
|
Light-Brown
|
R402B
|
Chlorodifluoromethane, Pentafluoroethane, Propane
|
Green-Brown
|
R403B
|
Chlorodifluoromethane, Octafluoropropane, Propane
|
Light Gray
|
R404A
|
Pentafluoroethane, Trifluoroethane, Tetrafluoroethane
|
Orange
|
R407C
|
Difluoromethane, Pentafluoroethane, Tetrafluoroethane
|
Brown
|
R408A
|
Chlorodifluoromethane, Trifluoroethane, Pentafluoroethane
|
Medium Purple
|
R409A
|
Chlorodifluoromethane, Chlorotetrafluoroethane,
Chlorodifluoroethane
|
Medium Brown
|
R410A
|
Difluoromethane, Pentafluoroethane
|
Rose
|
R414B
|
Chlorodifluoromethane, Chlorotetrafluoroethane,
Chlorodifluoroethane, Isobutane
|
Medium Blue
|
R416A
|
Tetrafluorethane, Chlorotetrafluoroethane, Butane
|
Yellow-Green
|
R417A
|
Pentafluoroethane, Tetrafluoroethane, Isobutane
|
Green
|
R500
|
Dichlorotrifluoromethane, Difluoroethane
|
Yellow
|
R502
|
Chlorodifluoromethane, Chloropentafluoroethane
|
Light Purple
|
R503
|
Chlorotrifluoromethane, Trifluoromethane
|
Blue-Green
|
R507
|
Pentafluoroethane, Trifluoroethane
|
Aqua Blue
|
R508B
|
Trifluoromethane, Hexafluoroethane
|
Dark Blue
|
Failure causing
|
Display mode 1
(indication lamp on display lamp board)
|
Display mode 2
(wired controller)
|
Display priority
|
Phenomenon
|
Communication failure
|
none
|
E5
|
1
|
shutdown
|
Drainage system failure
|
Timing lamp flash 4 times/8s
|
E4
|
2
|
shutdown
|
Phase failure, phase-loss or low voltage failure
|
Timing lamp lash 6 times/8s
|
E6
|
3
|
shutdown
|
Indoor temperature sensor abnormal (TA)
|
Timing lamp flash 1 times/8s
|
E1
|
4
|
shutdown
|
Indoor coil sensor abnormal(TE)
|
Timing lamp flash 2 times/8s
|
E3
|
5
|
shutdown
|
Outdoor coil sensor abnormal(TW)
|
Timing lamp flash 2 times/1s
|
E2
|
6
|
non-stop
|
Indoor
heating over-load protection
|
|
None
|
7
|
shutdown
|
Defrosting(not
failure)
|
Operation lamp flash
|
None
|
8
|
non-stop
|
Refrigerant
shortage
|
Flash 11 times and go out 2S
|
E0
|
11
|
shutdown
|
Failure causing
|
Display mode1
(indication lamp on display lamp board)
|
Display mode1
(failure lamp on control board)
|
Display mode3
(wired controller)
|
Display priority
|
Phenomenon
|
Communication failure
|
Flash 5 times and go
out 2S
|
Flash 2 times and go
out 2S
|
F1
|
1
|
shutdown
|
Wired controller communication failure
|
-
|
-
|
E5
|
1
|
shutdown
|
Drainage system failure
|
Flash 4 times and go
out 2S
|
-
|
E4
|
3
|
shutdown
|
Outdoor protection( Phase failure )
|
Flash6 times and go
out 2S
|
-
|
E6
|
2
|
shutdown
|
Outdoor protection (discharging over-temperature )
|
Flash 10 times and go
out 2S
|
Flash 10 times and go
out 2S
|
EA
|
7
|
shutdown
|
High
pressure protection
|
Flash 9 times and go
out 2S
|
Flash 1 times and go
out 2S
|
E9
|
6
|
shutdown
|
Low
pressure protection
|
Flash 9 times and go
out 2S
|
Flash 3 times and go
out 2S
|
E9
|
6
|
shutdown
|
Indoor
temp. sensor abnormal(TA)
|
Flash 1 times and go
out 2S
|
-
|
E1
|
4
|
shutdown
|
Indoor
coil sensor abnormal(TE)
|
Flash 3 times and go
out 2S
|
-
|
E3
|
5
|
shutdown
|
Outdoor
coil sensor abnormal(TW)
|
Flash 2 times and go
out 2S
|
Flash 2 times and go
out 2S
|
E2
|
8
|
non-stop
|
Outdoor
condensate temp. Sensor abnormal(TL)
|
Flash 7 times and go
out 2S
|
Flash 7 times and go
out 2S
|
E7
|
9
|
non-stop
|
Discharging
temp. sensor abnormal(TP)
|
Flash 8 times and go
out 2S
|
Flash 8 times and go
out 2S
|
E8
|
10
|
non-stop
|
Refrigerant
shortage
|
Flash 11 times and go
out 2S
|
Flash 11 times and go
out 2S
|
E0
|
11
|
shutdown
|