Senin, Agustus 19, 2013

Tabel warna freon



بِسْمِ اللّهِ الرَّحْمَنِ الرَّحِيْمِ

         Berikut ini saya lampirkan tabel warna dan kandungan freon yang beredar di pasaran,semoga dapat membantu dalam pemilihan saat membeli freon,agar dapat terhindar dari barang yang tidak bagus/tidak asli,semoga bermanfaat.



Tabel warna freon/refrigerant:

Refrigerant
Chemical Name
Color Code
R11
Trichlorfluoromethane
Orange
R12
Dichlorodifluoromethane
White
R13
Chlorotrifluoromethane
Light Blue
R113
Trichlorotrifluoroethane
Dark Purple
R114
Dichlorotetrafluoroethane
Navy Blue
R12/114
Dichlorodifluoromethane, Dichlorotetrafluoroethane
Light Gray
R13B1
Bromotrifluoromethane
Pinkish-Red
R-22
Chlorodifluoromethane
Light Green
R-23
Trifluoromethane
Light Blue Gray
R123
Dichlorotrifluoroethane
Light Blue Gray
R124
Chlorotetrafluoroethane
DOT Green
R134a
Tetrafluoroethane
Light Blue
R401A
Chlorodifluoromethane, Difluoroethane, Chlorotetrafluoroethane
Pinkish-Red
R401B
Chlorodifluoromethane, Difluoroethane, Chlorotetrafluoroethane
Yellow-Brown
R402A
Chlorodifluoromethane, Pentafluoroethane, Propane
Light-Brown
R402B
Chlorodifluoromethane, Pentafluoroethane, Propane
Green-Brown
R403B
Chlorodifluoromethane, Octafluoropropane, Propane
Light Gray
R404A
Pentafluoroethane, Trifluoroethane, Tetrafluoroethane
Orange
R407C
Difluoromethane, Pentafluoroethane, Tetrafluoroethane
Brown
R408A
Chlorodifluoromethane, Trifluoroethane, Pentafluoroethane
Medium Purple
R409A
Chlorodifluoromethane, Chlorotetrafluoroethane, Chlorodifluoroethane
Medium Brown
R410A
Difluoromethane, Pentafluoroethane
Rose
R414B
Chlorodifluoromethane, Chlorotetrafluoroethane, Chlorodifluoroethane, Isobutane
Medium Blue
R416A
Tetrafluorethane, Chlorotetrafluoroethane, Butane
Yellow-Green
R417A
Pentafluoroethane, Tetrafluoroethane, Isobutane
Green
R500
Dichlorotrifluoromethane, Difluoroethane
Yellow
R502
Chlorodifluoromethane, Chloropentafluoroethane
Light Purple
R503
Chlorotrifluoromethane, Trifluoromethane
Blue-Green
R507
Pentafluoroethane, Trifluoroethane
Aqua Blue
R508B
Trifluoromethane, Hexafluoroethane
Dark Blue

Kurang  lebihnya   mohon maaf,piss love  nd  gaul.


Jumat, Agustus 16, 2013

kode error indoor

السَّلاَمُ عَلَيْكُمْ وَرَحْمَةُ اللهِ وَبَرَكَاتُهُ

selamat pagi semua,saya akan lampirkan beberapa kode error untuk unit Ac type celling conceled merk AUX semoga bermanfaat :












Model : ALHD-C (H) 24/4

Failure causing
Display mode 1
indication lamp on display lamp board
Display mode 2
(wired controller)
Display priority
Phenomenon
Communication failure
none
E5
1
shutdown
Drainage system failure
Timing lamp flash 4 times/8s
E4
2
shutdown
Phase failure, phase-loss or low voltage failure
Timing lamp lash 6 times/8s
E6
3
shutdown
Indoor temperature sensor abnormal (TA)
Timing lamp flash 1 times/8s
E1
4
shutdown
Indoor coil sensor abnormal(TE)
Timing lamp flash 2 times/8s
E3
5
shutdown
Outdoor coil sensor abnormal(TW)
Timing lamp flash 2 times/1s
E2
6
non-stop
Indoor heating over-load protection

None
7
shutdown
Defrosting(not failure)
Operation lamp flash
None
8
non-stop
Refrigerant shortage
Flash 11 times and go out 2S
E0
11
shutdown

Model : ALHD-C (H) 36 s/d 60 /5
Failure causing
Display mode1
indication lamp on display lamp board
Display mode1
failure lamp on control board
Display mode3
wired controller
Display priority
Phenomenon
Communication failure
Flash 5 times and go out 2S
Flash 2 times and go out 2S
F1
1
shutdown
Wired controller communication failure
E5
1
shutdown
Drainage system failure
Flash 4 times and go out 2S
E4
3
shutdown
Outdoor protection( Phase failure )
Flash6 times and go out 2S
E6
2
shutdown
Outdoor protection (discharging  over-temperature )
Flash 10 times and go out 2S
Flash 10 times and go out 2S
EA
7
shutdown
High pressure protection
Flash 9 times and go out 2S
Flash 1 times and go out 2S
E9
6
shutdown
Low pressure protection
Flash 9 times and go out 2S
Flash 3 times and go out 2S
E9
6
shutdown
Indoor temp. sensor abnormal(TA)
Flash 1 times and go out 2S
E1
4
shutdown
Indoor coil sensor abnormal(TE)
Flash 3 times and go out 2S
E3
5
shutdown
Outdoor coil sensor abnormal(TW)
Flash 2 times and go out 2S
Flash 2 times and go out 2S
E2
8
non-stop
Outdoor condensate temp. Sensor abnormal(TL)
Flash 7 times and go out 2S
Flash 7 times and go out 2S
E7
9
non-stop
Discharging temp. sensor abnormal(TP)
Flash 8 times and go out 2S
Flash 8 times and go out 2S
E8
10
non-stop
Refrigerant shortage
Flash 11 times and go out 2S
Flash 11 times and go out 2S
E0
11
shutdown